Ice on the cold room floor or ceiling
Ice inside a walk-in is a defrost and drainage problem, and it becomes a safety problem the moment a staff member carries a full tray across it.
What it usually is
- 01A blocked or frozen defrost drain so meltwater refreezes where it lands
- 02Defrost terminating early, leaving ice to build cycle after cycle
- 03A door seal or curtain letting humid Cape air into the room
- 04A drain line run without a trap or with a fall the wrong way
- 05Evaporator fans running during defrost and blowing water outward
How to narrow it down
Clear the floor and mark it
Move stock off the iced area and put a cone or a mat down. Do not chip at the ice with a spade: evaporator and drain pipes run under the floor and through the panels in some rooms.
Find the drain
Trace the drain from the evaporator to where it exits. A frozen or sludged trap is the usual answer. Warm water and a gentle rod will clear it; a permanent fix often needs the drain re-run with proper fall and a heated section.
Check the defrost settings
Ask when the room was last serviced and whether the defrost times were changed. Longer or more frequent defrosts are sometimes set to hide a worn door seal, and the water has to go somewhere.
When to call
Call if ice returns within days of clearing, if the floor is slippery in a working kitchen, or if the room also struggles to hold temperature. Ice plus a temperature drift usually means the defrost system needs parts, not just a clearing.